Green Class Net Meter w/Dual Protocol Capabilities

Green Class Net Meter w/Dual Protocol Capabilities

  • Advanced 4-line display showing:
    • - kWh delivered, received and Net kWh
    • - kWh/Demand (with peak date and time)
    • - Power factor per Phase
    • - Real-time load in kW
    • - Amps per Phase
    • - Volts per Phase
  • On-board set-up option for:
    • - IP Address
    • - Meter date/time
    • - ID codes for EZ7, Modbus and BACnet
  • 0-2 volt output split-core current sensors allow for enhanced safety and accurate remote mounting of sensors up to 500 feet from meter without power interruption. (Optional solid-core current sensors available in 100 & 200 amp.)
  • Onboard diagnostics and verification system.
  • Two external meter inputs (water, gas, BTU, etc.) (Channels 5 & 6)
  • Phase loss alarm. (N.O. Contact)
  • Built-in RS-485 communications capability supports up to 52 Class 3200, 3400, 5000 meters and/or IDR interval recorders(or combinations not to exceed 52 devices per channel). 00
  • Cabling can be either daisy-chain or star configuration, 3-conductor, 18-22 AWG, up to 4,000 feet cable total per channel.
  • Communications include built-in RS-485 & Ethernet and optional telephone modem.
  • Protocols
    • - EZ7
    • - Modbus RTU
    • - Modbus TCP/IP
    • - BACnet MS/TP*
    • - BACnet IP*
    • - LonWorks FT-10 (Twisted Pair)*
  • Records kWh and kVARh delivered, kWh and kVARh received in first 4 channels. Data stored in 15-minute intervals for up to 72 days or 5-minute intervals for up to 24 days. Maintains interval data storage in a first-in, first-out format.
  • Compatible with E-Mon Energy software via EZ7 protocol for automatic meter reading, billing and profiling of interval energy data.
  • Meter is designed for use on both 3-phase, 3-wire (delta) and 3-phase, 4-wire (wye) circuits. Optional single-phase 3-wire configuration available.
  • Industrial grade green JIC steel enclosure with padlocking hasp and mounting flanges for indoor installation (stand alone). Knockouts: 1 1/16" (3/4" cond.) on bottom and 7/8" (1/2" cond.) on top of enclosure.
  • Optional outdoor NEMA 4X polycarbonate enclosure (standard) with padlocking hasp & mounting flanges for indoor/outdoor installation (stand alone) with one 1 1/16" KO on bottom of enclosure.
  • UL/CUL Listed. Certified by independent test lab to ANSI C12.20 national accuracy standards. (+/- 0.2% from 1% to 100% of rated load.)
  • CE Mark approved.
  • Meter meets or exceeds MID accuracy standards.
  • BACnet protocol is BTL certified. LonWorks protocol is LonMark Certified.
  • MV-90 Compatible (EZ7 only).
120/208-240V, 3 Phase
(Supplied with (3) Split-Core Current Sensors)

  • E50-208100-J*-N-KIT (100 Amp)
  • E50-208200-J*-N-KIT (200 Amp)
  • E50-208400-J*-N-KIT (400 Amp)
  • E50-208800-J*-N-KIT (800 Amp)
  • E50-2081600J*-N-KIT (1600 Amp)
  • E50-2083200J*-N-KIT (3200 Amp)
220/380V, 230/400V, 240/415V, 3 Phase
(Supplied with (3) Split-Core Current Sensors)

  • E50-400100-J*-N-KIT (100 Amp)
  • E50-400200-J*-N-KIT (200 Amp)
  • E50-400400-J*-N-KIT (400 Amp)
  • E50-400800-J*-N-KIT (800 Amp)
  • E50-4001600J*-N-KIT (1600 Amp)
  • E50-4003200J*-N-KIT (3200 Amp)
277/480V, 3 Phase
(Supplied with (3) Split-Core Current Sensors)

  • E50-480100-J*-N-KIT (100 Amp)
  • E50-480200-J*-N-KIT (200 Amp)
  • E50-480400-J*-N-KIT (400 Amp)
  • E50-480800-J*-N-KIT (800 Amp)
  • E50-4801600J*-N-KIT (1600 Amp)
  • E50-4803200J*-N-KIT (3200 Amp)
347/600V, 3 Phase, 4 W (Wye Config.)
(Supplied with (3) Split-Core Current Sensors)

  • E50-600100-J*-N-KIT (100 Amp)
  • E50-600200-J*-N-KIT (200 Amp)
  • E50-600400-J*-N-KIT (400 Amp)
  • E50-600800-J*-N-KIT (800 Amp)
  • E50-6001600J*-N-KIT (1600 Amp)
  • E50-6003200J*-N-KIT (3200 Amp)
Enclosure Options
Meters supplied standard in NEMA 4X outdoor enclosures. To order a different enclosure replace "R" in model number with optional enclosure specification.
JIC Steel Enclosure-Specify J
(Example: E50-208100-J01-N-KIT)