Class 5000 Three-Phase Advanced Smart Meter Engineering Specifications

Jan 01, 0001

The specifications below are designed to be cut and pasted into your engineering/ordering documents for easy specification of E-Mon D-Mon Class 5000 Smart meters.

  • Meter shall be fully electronic with 4-line LCD display showing kWh.
  • Meter shall use 0-2 volt output split-core current sensors to allow paralleling and/or mounting up to 500 feet from the meter. Sensors shall be of split-core configuration to allow installation without powering down. Sensors shall be available from 100 amp to 3200 amp. Sensors shall be optionally available in solid-core configuration (100 & 200 amp.)
  • Meter shall provide current sensor installation diagnostics indicator, phase error indicator and phase angle diagnostics on display.
  • Meter shall be field programmable for meter date/time, IP address and ID code for communication option and optional load control settings.
  • Meter shall be enclosed in a NEMA 4X polycarbonate enclosure (standard) with padlocking hasp & mounting flanges for indoor/outdoor installation (stand alone) with one 1 1/16" KO on bottom of enclosure. Optional heavy duty JIC steel enclosure available for indoor installation.
  • Meter shall be UL Listed/CUL Listed to latest applicable standards for safety.
  • Meter shall meet or exceed ANSI C12.20 accuracy standards.
  • Meter shall provide non-volatile memory to maintain reading during power outages.
  • Meter shall store interval data for kW and kVAR for up to 72 days in first-in first-out format. (Standard firmware.)
  • Meter shall operate as a slave device when used with Modbus or Lonworks options. Meter works as a master device on BACnet MS/TP.
  • Meter shall provide optional 5th & 6th channel for logging inputs from third-party metering devices (gas, water, BTU, etc.) Both channels provide interval data logging that can be read via E-Mon Energy software and Modbus.
  • Meter shall provide two (2) pulse outputs.
  • Meter shall be capable of daisy-chain or star connection using RS-485 communications in combinations of Class 3200s, 3400s, 5000s, IDR-8s, IDR-16s not to exceed 52 devices. Cabling shall be available through terminal block (3-conductor), 18-22 AWG, up to 4,000 cable feet total.
  • Meter shall be available with the following communication protocol & option packages:
RS-485 Port Ethernet Port Specify
EZ7 EZ7 Ethernet 01
Modbus RTU EZ7 Ethernet 02
BACnet MS/TP EZ7 Ethernet 03
EZ7 Modbus TCP/IP 04
EZ7 BACnet IP 05
Modbus RTU Modbus TCP/IP 06
Lonworks FT-10 EZ7 Ethernet 07
Lonworks FT-10 Modbus TCP/IP 08
EZ7 w/Telephone Modem EZ7 Ethernet 09
EZ7 w/Telephone Modem Modbus TCP/IP 10
EZ7 w/Telephone Modem BACnet IP 11